Application :–
Used in Transformer or other sealed tank while Storing / Transportation to provide constant N2 / Inert Gas pressure so as not to allow atmospheric air & moisture.
Working :–
Gas regulator is used to automatically maintains a positive pressure of 0.15 to 0.175 kg / cm.sq. or as desired inside the connected tank by help of Twin attached High Pressure gas cylinder.
In case pressure falls below 0.15 kg / cm.sq.(or as set) due to leakage or temperature variation. Regulator automatically allows required additional gas to flow from the attached High-Pressure gas cylinder (not standard part of our item). This builds up the pressure. Double Stage regulation minimizes the risk. To know the inlet & outlet pressure, gauges are attached of 2.5” (63 mm) dial size, generally confirming to IS 3624 for better readability.
Non Return Valve ( N.R.V.) ensures that no gas passes from cylinder one to another even when one of the gas cylinders gets empty. Safety valve at High-Pressure & Low-Pressure are attached so that if any unwanted pressure builds up in regulator is released.
L.P. hose normally 3600 mm. long is of PVC/ Rubber (1 No.) with ¼” B.S.P. female thread outlet connection of Brass for Tank End. H.P. hose (2 No.) is normally 800mm. long each of annealed copper pipe (3/16”*5/16”) fitted with brass socket of 5/8” B.S.P. male thread at cylinder end and 3/8” B.S.P. female thread at regulator end.
Complete assembly is packed in steel box with locking arrangement to avoid pilferage during shipment / transportation. Painted with two coats of anti corrosive paint both inside & outside. Followed by glossy white color inside to give a better readability back ground for gauge & outside of light grey shade confirming to 631 of IS:5 or any other as desired.
Model available for single cylinder connection also.
Model available with Flexible Cylider Pressure Hose of Teflon with S.S. Braid.
Testing :–
- Each assembly is tested for Functional & Leakage Test for 24 hrs by compressed air / gas after blocking outlet connection .
- H.P hose is tested at 130 ±10 kg / cm.sq. for 15 minutes.
- L.P hose is tested at 0.7 kg / cm.sq. for 15 minutes.
Mounting:- 4 Nos. slot are provided at 203*300 mm. p.c.d for M-12 bolts for mounting or as desired.
Identification :- Each Regulator bears S.No., Month, Year of manufacturing for identification.
Test Certificate :- Test Certificate is provided with each regulator for the above test performed.
Special features are:-
- After connecting Twin Cylinders by help of inlet copper hose. Pressure Guage shows the acting cylinder pressure .
- Final regulated outlet pressure is shown by L.P. Guage .
- N.R.V. attached at the outlet Rubber Hose (Tank End) assures that no gas comes out from the attached Tank through Regulator.
Important Note :- Products are under regular modification & improvement hence are liable to change . Drawing stated is for referance and to explain working / funtional aspect of product.